Permit Number: T08CM01553
Parcel: 14044018C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM01553
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2008 DAVE MANN FIRE REVIEW Approved
05/16/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; East District; 19,158 Square Feet Storage; $40,109.38
05/20/2008 TERRY STEVENS ZONING REVIEW Denied 05/20/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
05/20/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/30/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREFABRICATED METAL BUILDING: PROVIDE SIGNED AND SEALED CALCULATIONS AND DETAILS FOR THE VERTICAL AND LATERAL ANALYSIS, INCLUDING ALL FRAMING MEMBERS, FOUNDATIONS, AND SLABS.
06/09/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/09/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide energy code compliance calculations. Reference: Section 101.4, International Energy Conservation Code 2006.
3. Clarify the termination of the condensate drains for the roof top units Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
06/09/2008 ROBERT SHERRY WATER REVIEW Passed
06/10/2008 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2008 DELMA ROBEY APPROVAL SHELF Completed
11/18/2008 DELMA ROBEY OUT TO CUSTOMER Completed
11/18/2008 GERARDO BONILLA REJECT SHELF Completed