Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T08CM01553
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/16/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | Impact Fee's Do Apply; East District; 19,158 Square Feet Storage; $40,109.38 |
| 05/20/2008 | TERRY STEVENS | ZONING | REVIEW | Denied | 05/20/2008 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |
| 05/20/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/30/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREFABRICATED METAL BUILDING: PROVIDE SIGNED AND SEALED CALCULATIONS AND DETAILS FOR THE VERTICAL AND LATERAL ANALYSIS, INCLUDING ALL FRAMING MEMBERS, FOUNDATIONS, AND SLABS. |
| 06/09/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/09/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. Provide energy code compliance calculations. Reference: Section 101.4, International Energy Conservation Code 2006. 3. Clarify the termination of the condensate drains for the roof top units Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson. |
| 06/09/2008 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 06/10/2008 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/18/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 11/18/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/18/2008 | GERARDO BONILLA | REJECT SHELF | Completed |