Permit Number: T08CM01551
Parcel: 14044018C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM01551
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2008 DAVE MANN FIRE REVIEW Approved
05/16/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; East District; 1,025 Square Feet Office; 17,399 Square Feet Storage; $41,397.44
05/20/2008 TERRY STEVENS ZONING REVIEW Denied 05/20/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
05/20/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/30/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.02; ROOF FRAMING PLAN NOTES: NOTE 3 INDICATES MASONRY LINTELS PER SCHEDULE ON 4/S4.01. NO SCHEDULE FOUND. CLARIFY.
2. CALCULATIONS: TYPICALLY INDICATE ON CALCULATIONS WHERE BEAMS AND GIRDERS ARE LOCATED ON THE ROOF CALCULATION REFERENCE PAGE TO ASSIST IN PLAN REVIEW.
3. SHEET S1.02; CALCULATIONS: COLUMNS AT W10X30 ARE CALLED OUT AS HSS 5 1/4 X 5 1/4 X 1/8. SHOW CALCULATIONS AND VERIFY SIZE.
4. ENERCALC CALCULATIONS REFERENCE 2003 IBC. UPDATE AND VERIFY DESIGN MEETS 2006 IBC.
5. PREFABRICATED METAL BUILDING: PROVIDE SIGNED AND SEALED CALCULATIONS AND DETAILS FOR THE VERTICAL AND LATERAL ANALYSIS, INCLUDING ALL FRAMING MEMBERS, FOUNDATIONS, AND SLABS.
06/09/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for business occupancy (e.g. a drinking fountain). Reference: Section 1109.5.1, IBC 2006.
3. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. (See text at: http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). In addition, Accessible metering faucets shall remain open for a minimum of 10 seconds. Reference: Section 402.1, UPC 2006, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-2003.
4. Provide underground facility tracer wires per ARS 40-360.22.
06/09/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide energy code compliance calculations. Reference: Section 101.4, International Energy Conservation Code 2006.
3. Show how the fan coil, AH-1, is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
4. Provide an auxiliary drain pan or a secondary drain system for fan coil unit, AH-1. Reference: Section 307.2.3 IMC 2006.
5. Clarify the termination of the condensate drains for the roof top units Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
6. Provide information on the sequence of operation for the exhaust for restroom 0102 to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006.
06/09/2008 ROBERT SHERRY WATER REVIEW Denied 1. Provide a site drawing that shows the location and size of the water meter and the reduced pressure backflow preventer assembly for the water service.
2. A ¾" water meter is not available from Tucson Water; 5/8" and 1" water meters are available
06/10/2008 GERRY KOZIOL WWM REVIEW Denied 1. HERCULES SELF-STORAGE - OFFICE BLDG #1 (A)
2. NEED WASTEWATER 2ND FLOOR/WASTEWATER 8TH FLLOR REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - (DIAGONAL ACROSS LOS REALES BETWEEN 2 - PUBLIC MANHOLES)
3. NEED TO REVIEW PLUMBING PLAN (DOES NOT INCLUDE DRINKING FOUNTAIN SHOWN ON FLOOR PLAN)
4. NEED ADRESSING REVIEW (MAY BE PART OF PARENT PARCEL WITH ACCESS FROM LOS REALES)

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2008 VFLORES1 OUT TO CUSTOMER Completed