| 05/16/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01540 5/16/08 1. 600 MCM Al is good for 340A. It appears that there would be 429A with this project. |
| 05/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/23/2008 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |