Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2008 MARTIN BROWN FIRE REVIEW Approved
05/16/2008 HEATHER THRALL ZONING REVIEW Approved
05/16/2008 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/16/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
05/16/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied NEED STRUCTURAL CALS FOR HOOD SUPPORT FROM EXISTING TRUSSES.
05/16/2008 PAUL MACHADO ENGINEERING REVIEW Approved
05/16/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Wrap for the grease duct shall have been tested per ASTM E2336 and applied in accordance with the manufacturer's recomendations.
2. Show that the makeup air ducts within 18" of the hood comply with Section 506.3.1.2, IMC 2006.
3. The hood is exhausting 2700 CFM and the makeup air unit is supplying 2200 CFM. Where is the other 500 CFM of makeup are coming from? Reference Section 508.1, IMC 2006.
05/16/2008 ROBERT SHERRY WATER REVIEW Approved
05/16/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved