Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T08CM01540
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/16/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 05/16/2008 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/16/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 05/16/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | NEED STRUCTURAL CALS FOR HOOD SUPPORT FROM EXISTING TRUSSES. |
| 05/16/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Wrap for the grease duct shall have been tested per ASTM E2336 and applied in accordance with the manufacturer's recomendations. 2. Show that the makeup air ducts within 18" of the hood comply with Section 506.3.1.2, IMC 2006. 3. The hood is exhausting 2700 CFM and the makeup air unit is supplying 2200 CFM. Where is the other 500 CFM of makeup are coming from? Reference Section 508.1, IMC 2006. |
| 05/16/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/16/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/16/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |