Permit Number: T08CM01533
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01533
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section 804.1, UPC 2006 does not allow the installation of an indirect waste receptor inside of a cabinet; the receptor shall be "readily accessible for inspection and cleaning." Reference: Section 203.0 (Accessible).
2. The Pharmacy Area Plumbing Plan calls out detail 69/M1 for the water heater installation. The detail does not seem to be on sheet M1 but if it is to be shown or otherwise noted, a thermal expansion tank shall be included in the water heater installation per Section 608.3, UPC 2006.
07/21/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2008 DELMA ROBEY OUT TO CUSTOMER Completed
07/29/2008 SUE REEVES REJECT SHELF Completed