Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM01533
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/11/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Section 804.1, UPC 2006 does not allow the installation of an indirect waste receptor inside of a cabinet; the receptor shall be "readily accessible for inspection and cleaning." Reference: Section 203.0 (Accessible). 2. The Pharmacy Area Plumbing Plan calls out detail 69/M1 for the water heater installation. The detail does not seem to be on sheet M1 but if it is to be shown or otherwise noted, a thermal expansion tank shall be included in the water heater installation per Section 608.3, UPC 2006. |
07/21/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/29/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
07/29/2008 | SUE REEVES | REJECT SHELF | Completed |