Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01533
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/27/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/03/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. SHEET S1; HOLDOWN SCHEDULE: ELEVATION B AND DETAIL "b-b" REFER TO HOLDOWN SCHEDULE, BUT THE SCHEDULE DOES NOT SPECIFY WHICH HOLDOWN TO USE. WALL BRACING SCHEDULE INDICATES NO HOLDOWN TO BE USED. TO FACILITATE OUR INSPECTOR, PLEASE CLARIFY THESE ISSUES. |
| 06/09/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/16/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the hub drain complies with Sections 411.1 and 804.1, UPC 2006. 2. Coordinate the waste and vent plan with detail 16/M-1. The detail appears to show a wet vent connection for the sink but the waste and vent plan seems to indicate otherwise. Reference: Section 103.2.3, UPC 2006. |
| 06/16/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/20/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Equipment and circuitry is congested on Pharmacy Power Plan. Receptacles on Ckts 5 & 7 with no panel schedule. Electrical loads on Panels C1, NCR, and NCR1 but no panel schedules. 2. On Pharmacy Power Plan, correct "P12.20" to read "P12/2." 3. Add the electrical loads for T6 to H4-32,34,36. 4. With both Panels P9 and P12 added to the 45A circuit powering T6 and T7, phase A of this feeder is overloaded at 46A. 5. Feeder description for Panel P12 is overwritten on One Line Diagram. 6. Provide a disconnecting means for the Water Heater. |
| 06/26/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/10/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 07/10/2008 | SUE REEVES | REJECT SHELF | Completed |