Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/04/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/04/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/04/2008 | RBROWN1 | ADA | REVIEW | Denied | 4 AUGUST 2008 T08CM01503/COT CONVENTION CENTER REVIEWED BY RON BROWN ACCESSIBLE REVIEW - RESUBMITTAL ADAAG DENIED: SEE COMMENTS BELOW I. SHEET A0.0 A. OK II. SHEET A0.1: A. DETAIL 1: USE 3'-0" DIMENSION FOR TISSUE DISPENSER LOCATION B. OK C. OK III. SHEET A4.1: A. OK B. OK C. OK IV. SHEETS A5.1: A. DETAILS 1, 2 AND 3: ONE SET OF DOCUMENTS ONLY WERE REVISED TO COMPLY WITH ADAAG, PARAGRAPH 4.22.4, FIGURE 30(b). PLEASE PROVIDE TWO COMPLETE REVISED SETS. V. SHEETS A5.2: A. OK B. OK VI. SHEETS A3.3: A. EXISTING LAVATORIES ARE SPECIFIED TO HAVE HOT AND COLD WATER PIPING PLUS WASTE PIPING INSULATED, SHOULDN'T THE NEW LAVATORIES HAVE THE SAME SPECIFICATION REQUIREMENT FOR ACCESSIBLE LAVATORIES AS PER ADAAG 4.19.4? VII. SHEETS E7.0: A. OK STRUCTURAL NOTE: FONT APPEAL APPROVAL IS NOT ATTACHED WITH DRAWINGS. PLEASE INSURE ATTACHMENT OF FINAL APPROVAL IS RECEIVED WITH DRAWINGS. END OF REVIEW |
08/26/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed |