Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM01503
Parcel: 11720029A

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01503
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2008 RBROWN1 ADA REVIEW Denied 22 MAY 2008
T08CM01503/COT CONVENTION CENTER
REVIEWED BY RON BROWN

ACCESSIBLE REVIEW
ADAAG

DENIED: SEE COMMENTS BELOW

I. SHEET A0.0
A. DENOTE GOVERNING ACCESSIBILITY CODE; ADAAG 1994 EDITION. ACCESSIBILITY COMPLIANCE FOR THIS PROJECT WILL BE REVIEWED SOLELY AS PER ADAAG REQUIREMENTS.
II. SHEET A0.1:
A. DETAIL 1: USE 3'-0" DIMENSION FOR TISSUE DISPENSER LOCATION, VERTICAL BAR IS NOT ADAAG REQUIREMENT.
B. DETAIL 4: AS PER ADAAG, FIGURE 28, THE LAVATORY MAY ENCROACH INTO THE TOILET CLEAR SPACE.
C. DETAIL 7: SHOW THE MINIMUM AND MAXIMUM CLEAR SPACE POSITIONING AT THE LAVATORY AS PER ADAAG FIGURE 32.
III. SHEET A4.1:
A. DETAILS 2, 4 AND 6: SHOULDN'T THE ENTRY DOORS HAVE AN ELECTRONIC OPENING SYSTEM?
B. DETAIL 4: DOE THE PAPER TOWEL DISPENSERS MEET ADAAG 4.4, PROTRUDING OBJECTS?
C. INSURE ALL LAVATORIES MEET DIMENSIONAL REQUIREMENTS OF DETAIL 7/A0.1.
IV. SHEETS A5.1:
A. DETAILS 1, 2 AND 3: END TOILET STALLS WITH PARALLEL GRAB BARS DO NOT COMPLY WITH ADAAG, PARAGRAPH 4.22.4. THESE STALLS SHOULD BE MORE LIKE DETAIL 3.A5.2
V. SHEETS A5.2:
A. DETAILS 1 AND 2: SHOULDN'T THESE ENTRANCE DOORS HAVE AN ELECTRONIC OPERATIONAL OPENING SYSTEM?
B. DETAIL 3: PROVIDE ELECTRONIC OPENING SYSTEM FOR THE WOMEN'S TOILET ROOM.
VI. SHEETS A3.0, 3.1 AND 3.2:
A. INSURE ALL MODIFIED LAVATORIES HAVE PROPER PIPING INSULATION INSTALLED.
VII. SHEETS E7.0:
A. WHY NOT STROBES IN THE NORTH WEST TOILET ROOMS?

END OF REVIEW
05/22/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied LETTERING FONTS FOR ALL DRAWINGS TO BE MINIMUM OF 1/8" HIGH OR OBTAIN APPEAL FROM BUILDING OFFICIAL FOR 3/32" HIGH FONTS. APPROVED APPEAL MUST BE SUBMITTED WITH REVIEW DRAWINGS.
05/23/2008 MARTIN BROWN FIRE REVIEW Approved
06/09/2008 STEVE SHIELDS ZONING REVIEW Approved
06/13/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/13/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/13/2008 ROBERT SHERRY WATER REVIEW Approved
06/19/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/20/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2008 DELMA ROBEY OUT TO CUSTOMER Completed