Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2008 GERRY KOZIOL WWM REVIEW Approved
10/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the calculations for common ventilation systems (i.e. for each RTU serving multiple types of occupancies). Reference: Section 403.3.2, IMC 2006.
10/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Using your calculated demand of 41 GPM (29.5 fixture units), your chart indicates that the specified 1-1/4" supply to the two restrooms is undersized. The branch serving the restrooms has 22.5 fixture units and a demand of approximately 36 GPM; using your chart, a 1-1/2" supply is required. Also, considering that the flush valves operate for approximately 4 seconds per flush, the branch piping to the flush valves is undersized with respect to water velocity. Reference: Section 610.1, UPC 2006.
10/15/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied Provide floodplain use permit along with building permit with next submittal.