Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM01481
Parcel: 128010190

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01481
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/22/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied Unable to approve building plan at this time. Please submit floodplain use permit with next submittal.

If you have any questions, please contact my if you have any questions bianca.ramirez@tucsonaz.gov or 837-4928.
08/25/2008 DAVE MANN FIRE REVIEW Approved
08/26/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/26/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/29/2008 STEVE SHIELDS ZONING REVIEW Approved
09/04/2008 ROBERT SHERRY WATER REVIEW Approved
09/04/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise detail 10/P-2 to eliminate the termination of the condensate to a splash block on the roof. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Revise the ventilation calculations, showing the floor area for each room (not "POS"). The minimum ventilation rate for the checkout area is 0.3 CFM/SF (Retail, Basement and Street). Provide the calculations for common ventilation systems. Reference: Sections 401.2, 403.3, and 403.3.2, IMC 2006
09/04/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; detail 5/P-3 shows a shut-off valve and a check valve located between the water heater and the vacuum breaker. Revise the location of the vacuum relief for the water heater to conform to the manufacturer's listing information (i.e. with no valves between the vacuum relief and the water heater). Reference: Sections 310.4 and 608.7, UPC 2006.
2. The submitted water pipe sizing calculations appear to be for a flush tank system, not a flush valve system. Using your calculated demand of 50 GPM (48.75 fixture units), your chart indicates that the specified 1-1/4" supply would have a velocity of nearly 13 feet per second and a head loss of 20 PSI per 100 feet. Similarly, the 1-1/4" branch to the restrooms will have a demand of approximately 45 GPM (39.25 fixture units) resulting in a velocity greater than 11 feet per second and a head loss of about 14 PSI per 100 feet. Also, considering that the flush valves operate for approximately 4 seconds per flush, the branch piping to the flush valves is undersized with respect to water velocity. Reference: Section 610.1, UPC 2006.
3. Revise the plumbing drawings to reflect the actual condition of the existing water service to the space (e.g. detail 9/P-3). The calculations shall reflect the actual size of the existing water meter and backflow preventer for the building as well as any water demand from other suites that are served by the same service. Reference Sections 103.2.3 and 610.1, UPC 2006.
09/17/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/19/2008 GERRY KOZIOL WWM REVIEW Denied NEEDS WASTEWATER 5TH FLOOR CREDIT EVALUATION

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2008 CPIERCE1 OUT TO CUSTOMER Completed
09/26/2008 SUE REEVES REJECT SHELF Completed