Permit Number: T08CM01471
Parcel: 14041098A

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T08CM01471
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide all check and shut off valves required for operation of the sump pumps. Reference: Sections 710.4 and 710.6, UPC 2006.
2. Show how the sump is to be maintained at atmospheric pressure at all times (i.e. where is the vent?) Reference: Section 710.8, UPC 2006.
3. Show how the drainage piping is to be installed. Reference: Section 710.7, UPC 2006.
04/20/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/29/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2009 GERARDO BONILLA OUT TO CUSTOMER Completed