Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01447
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/09/2008 | ERIC NEWCOMB | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/09/2008 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/22/2008 | CPIERCE1 | WATER | REVIEW | Passed | |
| 05/22/2008 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/22/2008 | CPIERCE1 | WWM | REVIEW | Passed | |
| 05/22/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM01447 5/9/08 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 3. Account for new Water Heater on Plumbing plans. 4. Specify the floor lighting. |
| 05/22/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/22/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/22/2008 | MARTIN BROWN | FIRE | REVIEW | Approved |