Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T08CM01436
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T08CM01436 6/5/08 1. "Temporary power is limited to 90 days for the purposes of applying Article 590 of the National Electrical Code. Estimated duration of installation 6 months per Applicant. Reference Keynote 2." THIS COMMENT WAS MADE ON THE SUBMITTAL OF 5/5/08. Sheet E1.1 conduits on Keynotes 1 and 2, Type W Cable not permitted. Reference NEC 400.7, 400.8 (1) and (4), 590.3 (B). 3. Provide power requirements for the chillers. Otherwise, there is no way for the Electrical Plans Examiner to evaluate Ground Fault and Short Circuit Protection, or conductor ampacity. 4. Put the electrical plans on a full sized sheet, minimum font size 1/8". 5. Demonstrate that the electrical service is not overloaded. 6. Intent of Keynote 6 is not clear. If this 100A switch with 60A fuses is to be used for the portable chiller pump power, then there then Portable Chiller connections 1 and 2 do not appear to be necessary. Please clarify all equipment. |