Permit Number: T08CM01436
Parcel: 11711076A

Address:
126 E ALAMEDA ST

Review Status: Completed

Review Details: OTHER

Permit Number - T08CM01436
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01436 5/5/08

1. Plans shall be sealed by a Registered Electrical Engineer.
2. Temporary power is limited to 90 days for the purposes of applying Article 590 of the National Electrical Code. Estimated duration of installation 6 months per Applicant. Reference Keynote 2.
3. Provide power requirements for the chillers. Otherwise, there is no way for the Electrical Plans Examiner to evaluate Ground Fault and Short Circuit Protection, or conductor ampacity.
4. Put the electrical plans on a full sized sheet, minimum font size 1/8".
5. Demonstrate that the electrical service is not overloaded.
6. Intent of Keynote 6 is not clear. If this 100A switch with 60A fuses is to be used for the portable chiller pump power, then there then Portable Chiller connections 1 and 2 do not appear to be necessary. Please clarify all equipment.
05/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved