Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T08CM01433
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/28/2008 | HENRY DURAZO | BUILDING-RESIDENTIAL | REVIEW | Denied | 1. Permits are required for covered patio build attached to guest house. 2. Relocate gas line from under roof structure. 3.Over head electrical service shall be 8' [feet] min. from proposed roof per IRC sec E3504.2 4.Specify water line type and size, on site plan. 5.Provide exterior light and ventilation tositting room, delete clothes closet in this room. 6.Complete plumbing plan, show all waste lines and fittings. 7.Provide complete water distribution plan. 8.Clarify electric panel schedule,whats existing/new, cross reference circuit # to lay-out on electrical plan. 9.Is a new 100 amp service added to existing guest house? If so show how unit is currently feed, and location of junction box. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/09/2008 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 06/09/2008 | GERARDO BONILLA | REJECT SHELF | Completed |