Permit Number: T08CM01433
Parcel: 106010840

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T08CM01433
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2008 GERRY KOZIOL WWM REVIEW Approved
05/28/2008 HENRY DURAZO BUILDING-RESIDENTIAL REVIEW Denied 1. Permits are required for covered patio build attached to guest house. 2. Relocate gas line from under roof structure. 3.Over head electrical service shall be 8' [feet] min. from proposed roof per IRC sec E3504.2 4.Specify water line type and size, on site plan. 5.Provide exterior light and ventilation tositting room, delete clothes closet in this room. 6.Complete plumbing plan, show all waste lines and fittings. 7.Provide complete water distribution plan. 8.Clarify electric panel schedule,whats existing/new, cross reference circuit # to lay-out on electrical plan. 9.Is a new 100 amp service added to existing guest house? If so show how unit is currently feed, and location of junction box.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2008 THAUSER1 OUT TO CUSTOMER Completed
06/09/2008 GERARDO BONILLA REJECT SHELF Completed