Permit Number: T08CM01421
Parcel: 10309064B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01421
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHOW TYPICAL MANUFACTURER'S DETAIL FOR LIGHT POLE FOOTING (LIGHT POLE UNDER 20' TALL).
05/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01421 5/5/08

1. Provide a detail for the pole and foundation.
2. Provide a lighting fixture schedule. Identify the exact wattage for the new fixture.
3. Provide panel and circuit number for new lighting.
4. Provide panel schedule and load calculations.
5. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
05/05/2008 DAVE MANN FIRE REVIEW Approved