Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01413
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/01/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/02/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/02/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/02/2008 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/02/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/02/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/02/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 06/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/19/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |