Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01381
Parcel: 105102520

Address:
4262 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01381
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. SHEET A1; FLOOR PLAN: SECTION 03/A7 CUT ON SOUTH WALL SHOULD BE CHANGED TO 04/A7.
06/30/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy code compliance calculations (for the building envelope). Note that the building is not located in Marana; use Pima County, less than 4,000 ft. Reference: Section 101.4, International Energy Conservation Code 2006.
06/30/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Justify the use of a 1/8" per foot slope for the building drain. Reference: Section 708.0, UPC 2006.
07/07/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/11/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Retail "D" - Rillito Crossing Marketplace
T08CM01381
Building Plan (2nd Review)

TRANSMITTAL DATE: July 11, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved revised development plan. Please submit two copies of the approved and stamped revised development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm01381.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
07/18/2008 GERRY KOZIOL WWM REVIEW Denied 1. SHELL BUILDING
2. NO TI'S UNTIL SEWER FEES ARE PAID
3. NO WATEWATER PLUMBING STUB-OUTS WITH THE EXCEPTION OF 1 MOP SINK
4. NEEDS TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - NEEDS DEQ REVIEW & APPRV TO CONSTRUCT PRIVATE SEWER IF OVER 3000 GALLONS/DAY - NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2008 CPIERCE1 OUT TO CUSTOMER Completed
07/25/2008 SUE REEVES REJECT SHELF Completed