Permit Number: T08CM01369
Parcel: 12201001B

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T08CM01369
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
04/29/2008 ANY WWM REVIEW Active
04/30/2008 STEVE SHIELDS ZONING REVIEW Approved
04/30/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/30/2008 DAVE MANN FIRE REVIEW Approved
05/02/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/02/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01369 5/2/08

1. Cut sheet for HydroTrack describes 7.2 KW equipment. Load on panel achedule only accounts for 5.4 KW. Please clarify.
2. Cut sheet for HydroTrack describes 45A equipment. Conductor is only good for 35A.
3. Fill in the electrical load for Ckt A-38 on the panel schedule.
4. A-26 powers receptacles in Office, not just phone board.
5. Add the following note on a prominent place on the plans: "All work in patient care areas shall comply with NEC 517.13."
05/02/2008 ROBERT SHERRY WATER REVIEW Approved
05/02/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/02/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved