Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL TI
Permit Number - T08CM01369
Review Name: COMMERCIAL TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active | |
| 04/29/2008 | ANY | WWM | REVIEW | Active | |
| 04/30/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/30/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 04/30/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/02/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/02/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01369 5/2/08 1. Cut sheet for HydroTrack describes 7.2 KW equipment. Load on panel achedule only accounts for 5.4 KW. Please clarify. 2. Cut sheet for HydroTrack describes 45A equipment. Conductor is only good for 35A. 3. Fill in the electrical load for Ckt A-38 on the panel schedule. 4. A-26 powers receptacles in Office, not just phone board. 5. Add the following note on a prominent place on the plans: "All work in patient care areas shall comply with NEC 517.13." |
| 05/02/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/02/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/02/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |