Permit Number - T08CM01363
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a duct smoke detector for AC-2. 2. Provide structural calculations and details to show that the installation of AC-1 and AC-2 will not damage the building. 3. Provide information on the sequence of operation for the restroom exhaust fans to show that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006 |
| 04/29/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/29/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location of the water meter and the new reduced pressure backflow assembly noted in the plumbing water calculations. |
| 04/29/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED STRUCTURAL REVIEW OF 2 NEW ROOF TOP UNITS THAT HAVE BEEN ADDED TO EXISTING ROOF PURLINS. |
| 04/29/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 04/29/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The branch piping size called out for the urinal flush valve will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 2. Provide a floor drain in restroom 111. Reference: Section 411.2, UPC 2006. |
| 05/27/2008 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 05/27/2008 | VFLORES1 | ZONING | REVIEW | Needs Review | |
| 05/27/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |