Permit Number: T08CM01363
Parcel: 10703143A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01363
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2008 MARTIN BROWN FIRE REVIEW Approved
04/29/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a duct smoke detector for AC-2.
2. Provide structural calculations and details to show that the installation of AC-1 and AC-2 will not damage the building.
3. Provide information on the sequence of operation for the restroom exhaust fans to show that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006
04/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/29/2008 ROBERT SHERRY WATER REVIEW Denied Show the location of the water meter and the new reduced pressure backflow assembly noted in the plumbing water calculations.
04/29/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. NEED STRUCTURAL REVIEW OF 2 NEW ROOF TOP UNITS THAT HAVE BEEN ADDED TO EXISTING ROOF PURLINS.
04/29/2008 PAUL MACHADO ENGINEERING REVIEW Approved
04/29/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The branch piping size called out for the urinal flush valve will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
2. Provide a floor drain in restroom 111. Reference: Section 411.2, UPC 2006.
05/27/2008 VFLORES1 WWM REVIEW Needs Review
05/27/2008 VFLORES1 ZONING REVIEW Needs Review
05/27/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review