Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01351
Parcel: 13414001K

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01351
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
04/28/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006.
2. Revise the font size used on the drawings (in mechanical plan) to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
04/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/28/2008 ROBERT SHERRY WATER REVIEW Approved
04/28/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/28/2008 LOREN MAKUS ENGINEERING REVIEW Approved
04/28/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the font size used on the drawings (in plumbing plan) to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006
04/28/2008 DAVE MANN FIRE REVIEW Approved
04/28/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/30/2008 GERRY KOZIOL WWM REVIEW Approved