Permit Number: T08CM01335
Parcel: 115155390

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM01335
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T08CM01335

6/09/08 768 W. CALLE ADELANTO

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



FOUNDATION PLANS:

1. PROVIDE FOOTING FOR BATH ROOM.

FLOOR PLANS:

1. PROVIDE DIMENSIONS TO LOCATE THE INTERIOR WALLS. SEE R304.3

2. PROVIDE DETAILS FOR THOSE WHICH ARE TO BE "VERIFIED IN THE FIELD."

3. PLEASE JUSTIFY THE WINDOW U-VALUE OF .65 WITH THE 4" ROOF INSULATION AND MSSONRY WALLS.

STRUCTURAL PLANS:

1. ROOF FRAMING / A-01 ; THE RAFTER REINFORCEMENT APPEARS TO BE INADEQUATE. PLEASE JUSTIFY.

2. ROOF FRAMING PLAN / A-01 ; HOW WILL THE EXISTING WALLS BE REPAIRED?

3. ROOF FRAMING PLAN / A-01 ; WHAT IS THE R-VALUE OF THE INSULATION IN THE ROOF? IN THE WALL? WINDOW U-VALUE? RES-CHECK? IRC CHAPTER 11?

4. ROOF FRAMING PLAN / A-01 ; PLEASE SIZE THE SCUPPERS. UPC APPENDIX D AND CHAPTER 11.

SECTIONS - DETAILS - MISC. NOTES:

1. ON STANDARD DETAIL SHEETS, CROSS-OUT ALL DETAILS THAT DO NOT APPLY OR WERE NOT USED.

2. PROVIDE A DETAIL SHOWING THE CONSTRUCTION OF THE NEW PARAPET AND IT'S BRACING.

3. NOTES / S-01 ; HOW DOES "ALL GYPSUM WALLBOARD USED AS A BASE FOR HARD SURFACE FINISHES IN SHOWERS….." COMPLY WITH R702.4.2 RE: CEMENT, FIBER-CEMENT, AND GLASS MAT GYPSUM BACKERS.

4. NOTES / S-01 ; THE FASTENER SCHEDULE IS TABLE R602.3(1) AND NOT ON PAGE 104.

5. PROVIDE A CROSS SECTION OF THE PROPOSED INTERIOR WALLS.

6. FINISH HARDWARE NOTE #1 / A-01 ; PROVIDE THE BUILDING STANDARDS.

7. FLOORING NOTE #1 ; WHERE IS SUB-FLOORING USED?

8. INTERIOR DOORS / A-01 ; PROVIDE THE PAMPHLET WITH THE DOOR HARDWARE REQUIREMENTS.

9. 4 / A-03 ; PLEASE CHANGE THE INCH MARKS THAT USE FOOT MARKS TO INCH MARKS.

10. PROVIDE THE LOCATION ON THE PLANS WHERE THE "VERIFY IN THE FIELD" DETAILS MAY BE FOUND.

11. GENERAL NOTES / A-01 ; IRC 2203 DOESN'T APPLY TO THERMAL OR ACCOUSTIC INSULATION. PLEASE CO-ORDINATE.

12. GENERAL NOTES / A-01 ; DELETE 1994 UBC AND REFERENCES TO IT.

13. 4 / A-03 ; BLOCKING SHOULD COVER THE ENTIRE WIDTH OF THE FRAMING MEMBER AND NOT BE INSTALLED FLAT.

14. LINTEL SCHEDULE / A-03 ; 9"X13.4 CHANNEL DOESN'T APPEAR TO BE ADEQUATE TO SPAN 20'. PLEASE JUSTIFY.

15. OPENING SCHEDULE U.N.O. / A-03 ; THE LINTELS FOR THE 2X4 STUD OPENINGS APPEAR TO BE INADEQUATE. PLEASE JUSTIFY.





IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2008 VFLORES1 OUT TO CUSTOMER Completed