Permit Number: T08CM01330
Parcel: 122173090

Review Status: Active

Review Details: RESUBMITTAL - SITE

Permit Number - T08CM01330
Review Name: RESUBMITTAL - SITE
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2008 TERRY STEVENS ZONING REVIEW Approved
11/20/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
11/25/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. The minimum required text size for archiving purposes is 12 point (0.12"). Revise the label for the trash enclosure on the landscape plan to meet this standard.

2. A street landscape border, per Sec. 3.7.2.4 of the LUC, is a landscape area running the full length of the street property line(s) bounding the site except for points of ingress-egress. The area between the private driveway/ PAAL and the paved access for trash trucks is not used for either vehicular or pedestrian access and must be landscaped. Revise plans to show landscaping and irrigation within the triangular-shaped area to the east of the trash truck access and immediately south of the pedestrian sidewalk which accesses the trash enclosure. It is recommended that the entire area between this pedestrian sidewalk and the street property line and between the PAAL and the trash truck access be landscaped to make up for nearly 50 percent of the street frontage of the site being paved for access points.

3. The vehicle parking space adjacent to the trash receptacle must be screened from the Belleview Street right-of-way. Label on the landscape plan the required 30-inch high screen. LUC Table 3.7.2-I

4. In the landscape calculations on sheet L-1 revise the information which states "Street Landscape Border (east side)..." to read "Interior Landscape Border (east side)...".
12/12/2008 LOREN MAKUS ENGINEERING REVIEW Denied December 12, 2008
The previous comments have been addressed. However, the differential grading issue discussed on the grading plan will need to be resolved before the site plan is approved.
12/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to include the following information:
a. the location and size of the water meters
b. the location of the main water lines
c. the location and size of the public sanitary sewer and
d. the location, invert, and rim elevation of the upstream and downstream manholes.
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section R106.1, IRC 2006.
2. Revise the site drawing to show the location of the proposed point of connection for the building sewer (or sewers). Reference Section R106.1, IRC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2008 SUE REEVES REJECT SHELF RECEIVED