Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM01330
Parcel: 122173090

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T08CM01330
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2008 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM01330
3139 E. Bellevue St.
Site Plan -- Apartments

TRANSMITTAL DATE: 05/16/08

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.



1. DS 2-02.2.1.7 The following comments can be used for submittal for the required Design Development Option (DDO).

South elevation of buildings #1 and #16
The required street setback per LUC Sec. 3.2.6.5.A is 20' or 1 ½ times the height of the proposed wall. The wall height of 24'-10 1/2" requires a street setback of 37'-3 3/4" the owner proposes a setback of 36'-3" . The wall height of 22'-1 1/2" requires a street setback of 33'-2 1/4" the owner proposes a setback of 29'-6 ½".

North elevations of buildings #8 and #9.
The required perimeter yard setback per LUC Sec. 3.2.6.4 is 10' or ¾ times the height of the proposed wall. The wall height of 24'-10 1/2" requires a setback from the north property line of 18'-7 7/8" the owner proposes a setback of 17'-1". The wall height of 22'-1 1/2" requires a setback from the north property line of 18'-7 7/8" the owner proposes a setback of 10'-4 ½".

The DDO must be completed and approved prior to approval of this site plan. Add a note stating the DDO case number, date of approval, what the DDO is for, and any conditions of approval. Add the DDO case number near the lower right hand corner of the site plan and all other sheets..

2. DS 2-02.21. The backup spur indicated must have a clear area behind the curb of three (3) feet. The indicated bollards appear to be less than 3' from the curb. Provide dimension.

3. DS 2-02.2.1.12 The pedestrian circulation path (sidewalk) must continue onto the trash enclosure.


4. Per your response letter zoning acknowledges that a DSMR is being applied for in regards to the following two comments. Zoning cannot approve the site plan until the DSMR is approved. Once the DSMR is approved add a note to the plans with the DSMR case number, date of approval, what the DSMR is for, and any conditions of approval. Add the DSMR case number near the lower right hand corner of the site plan and all other sheets.

Per DS 2-08.4.1.F Sidewalks or pedestrian refuge areas may not be located between any motor vehicle parking space and the PAAL providing access to that space.

Per DS 2-08.4.1 Sidewalks within a project must be physically separated from any vehicular travel lane by means of curbing, grade separation, barriers, railings, or other means. The wedge curb proposed is not considered a physical separation.

5. The indicated ridge height on the foot print of buildings 1 and 2 (24'-4") does not match the cross section nor buildings 15 and 16 (24'-10 1 ½"). Revise

The wall height on the foot print of building 16 (22'-1 ½") does not match the north elevation top of wall height (21'-7 1 ½"). Revise.

The DDO comments have been based on the greater dimension for both walls. If this is incorrect a revision to the DDO comments will be required.

5. Clearly indicate on the typical parking detail the surfacing material used for the parking spaces.. Per LUC 3.3.7.3 Surfacing Requirements. All vehicular use areas shall be surfaced with one (1) of the following materials.
A. Asphaltic concrete.
B. Cement concrete.
C. A penetration treatment of bituminous material and seal coat of bituminous binder and mineral aggregate.



If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08CM01330-2.doc
08/21/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 1. At the raised marked crossings, maintain a min 4' clear accessible route, move the 2' wide detectable warning strip in line with the wedge curb.
2. Provide a large scale detail of the sidewalk ramps of the raised marked crossing showing all dimensions, slopes and detectable warnings as required by 2006 IBC/ICC 117.1, Sections 405 and 406.
08/29/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. The minimum required text size for archiving purposes is 12 point (0.12"). Revise all lettering and dimensions on the landscape plan which does not meet this standard.

2. A street landscape border, per Sec. 3.7.2.4 of the LUC, is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress. The trash receptacle access route may not be located within the required landscape border. Revise plan accordingly.

3. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border or fraction thereof. Revise the landscape border tree calculations along both east and west property lines to indicate that with 300 feet of interior landcape border a total of 10 canopy trees are required within the east and the west interior landcape borders. LUC 3.7.2.4

4. Grading, hydrology, and landscape structural plans are to be integrated to make maximum use of site
storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of
all runoff, from individual catch basins around single trees to basins accepting flow from an entire
vehicular use area or roof area. LUC 3.7.4.3.B
09/16/2008 LOREN MAKUS ENGINEERING REVIEW Denied September 18, 2008
T08CM01330
Bellevue Apartments site plan
Loren Makus, EIT

The site plan has been reviewed and not approved at this time. The grading plan included with the site plan was examined as part of the site plan review but was not reviewed at this time. The grading plan and associated documents must be submitted as a grading permit application.

1. Clearly dimension the backup spur for the parking spaces adjacent to units 8 and 9 to ensure that sufficient space is provided for the backup spur overhang.

Additional comments may be forthcoming once the required information for site plans has been provided.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2008 CPIERCE1 OUT TO CUSTOMER Completed
11/17/2008 SUE REEVES REJECT SHELF Completed