Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01301
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/23/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/23/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plans and schedules. 2. Provide calculations to show that the common ventilation system (AC-8) is sized in accordance with Section 403.3.2, IMC 2006. |
| 04/23/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/23/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. accessible space for water closets not in compliance, ansi 604.3 2. epoxy paint on gypsum board not acceptable, use FRP, C.T. etc. Epoxy Paint will peal off in a year. 3. rework all toilet accessory dimensions as per ansi 117.1, chapter six. 4. insulate pipes at all lavoratories. 5. And any other accessible compliances required by code, please recheck all elements. |
| 04/23/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006 |
| 04/23/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/29/2008 | DROBEY1 | WATER | REVIEW | Needs Review | |
| 04/29/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 04/29/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 04/29/2008 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/29/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 04/29/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/29/2008 | DELMA ROBEY | REJECT SHELF | Completed |