Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01278
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/23/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. LAVATORY ACCESSIBLE SPACE NOT IN COMPLIANCE WITH ANSI STANDARD 606.2. 2. LAVATORY ENCROACHING ON WATER CLOSET SPACE. |
04/23/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006 |
04/23/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006. 2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for business occupancy. 3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
04/23/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide information regarding the water meter (size) and if existing, the backflow preventer (size and location). |
04/24/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/24/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
05/15/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/15/2008 | GBONILL1 | WWM | REVIEW | Needs Review | |
05/15/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
05/15/2008 | GBONILL1 | FIRE | REVIEW | Needs Review |