Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01278
Parcel: 12902091D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01278
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. LAVATORY ACCESSIBLE SPACE NOT IN COMPLIANCE WITH ANSI STANDARD 606.2.
2. LAVATORY ENCROACHING ON WATER CLOSET SPACE.
04/23/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006
04/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for business occupancy.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
04/23/2008 ROBERT SHERRY WATER REVIEW Denied Provide information regarding the water meter (size) and if existing, the backflow preventer (size and location).
04/24/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
04/24/2008 JASON GREEN ENGINEERING REVIEW Approved
05/15/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/15/2008 GBONILL1 WWM REVIEW Needs Review
05/15/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/15/2008 GBONILL1 FIRE REVIEW Needs Review