Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01237
Parcel: 126210050

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM01237
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2008 GERRY KOZIOL WWM REVIEW Approved
05/16/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM01237 Guest House

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes).

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

SITE PLAN:

1. Indicate the location of a pool barrier (perhaps by others) separating the dwelling from the pool, 2006 IRC Amendment Section AG102.

STRUCTURAL PLANS:

1. Specify weight of roof system items (for example, weight of selected tile). Provide ICBO evaluation report number and manufacturer of all concrete or clay-type roofing, or note the material weight for calculating roof loads, R301.1.3.
2. The 6x10 Porch beams require DF#1 notation for a clay tile roof load, R802.
3. The 2x8 @ 24" OC Porch rafters appear undersized for a clay tile roof load. Provide rafter sizes and spacing in compliance with Table R802.5.1.

SECTIONS - DETAILS:

1. Calculate the attic ventilation using 1 to 150 of attic area in compliance with R806.2. Note that upper space vents provide 50% to 80% of the required ventilating area when applying the reduced area calculation.
2. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing when eave venting is used, R806.3. This may be accomplished w/ baffles.

PLUMBING PLANS:

1. The pool equipment and water heater branch (1-1/2") is undersized for a developed length of 200' from meter (requires upgrading), UPC 1217.2, & Table 12-8.

MECHANICAL PLANS:

1. Show bathroom exhaust fan minimum 50 CFM rating R303.3 and M1507.3.

ELECTRICAL PLANS:

1. Specify recessed lighting with 3" separation from combustibles or IC listing, R808, and compliance with energy efficiency leakage, N1102.4.3.
2. Show the Pool Storage receptacle outlet with ground fault circuit interrupting protection or change to monoplex for water heater control only, E3802.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2008 CPIERCE1 OUT TO CUSTOMER Completed