Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01230
Parcel: 105102430

Address:
555 E WETMORE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01230
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2008 STEVE SHIELDS ZONING REVIEW Approved
04/18/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/18/2008 PAUL MACHADO ENGINEERING REVIEW Approved
04/18/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/18/2008 DAVE MANN FIRE REVIEW Approved