05/08/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date:
Activity:
Address:
Applicant:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:
3. Revise site plan to show porch roof connecting the existing building to the proposed building.
4. Clarify construction type VN.

FLOOR PLANS:
5. Specify safety glazing in hazardous locations (less than 60" above tub/shower floors) R308.4.

FOUNDATION PLANS:
6. All exterior framed walls require continuous concrete footings min. 12" below grade, R319.1, R403.1.6.
7. Landing or floor surface required at all exterior doors, R311.4.3.

STRUCTURAL PLANS:
8. Specify gable-end bracing with connections to the structure, R802.10.3.
9. Show scissor truss to wall connection using (TC) slotted ties having a resistance to uplift of not less than 175 pounds, R802.10.5.
10. Provide an attic space ventilation calculation and note the size and location of all attic vents needed to comply, R806.2.

PLUMBING PLAN:
11. Sleeves are required when a gas line passes through concrete, UPC 1211.1.5.
12. Specify slope of building drain and verify height of existing sewer line, UPC 718.1.
13. Specify location and diameter of proposed water service line to existing house, UPC Table 6-5.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review