Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01221
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SECTION 1/A3, ADD BRACE TO VERTICAL STUD AT SUSPENDED CEILING |
| 04/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/17/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/17/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 04/22/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 04/22/2008 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 04/22/2008 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/22/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 04/22/2008 | CPIERCE1 | FIRE | REVIEW | Needs Review |