Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T08CM01208
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/17/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 17 APRIL 2008 T08CM01208/PARKING BUILDING REVIEWED BY RON BROWN STRUCTURES REVIEW 2006 IBC/ICC 117.1 DENIED: SEE COMMENTS BELOW I. COVER SHEET, SITE PLAN, 1 0F 3: A.PROVIDE LIST OF REGULATORY COMPLIANCE CODES B.PROVIDE BUILDING DATA FORM C.PROVIDE SHEET INDEX D.EAST WALL ,TO BE 1 HOUR RATED AS PER IBC 2006, TABLE 602 AND SHALL EXTEND 30" ABOVE ROOF DECK; 2006 IBC, SECTION 704.11.1 E. PROVIDE AND IDENTIFY ACCESSIBLE ROUTE THROUGHOUT SITE TO ALL BUILDING ENTRANCES AND EXITS AND PARKING FACILITIES AND TO NEAREST PUBLIC TRANSPORTATION POINT AS PER ICC 117.1, SECTION 402 1.SHOW LOCATION OF NEAREST PUBLIC TRANSPORTATION DROP OFF POINT. 2.PROVIDE SPOT GRADES THROUGHOUT ACCESSIBLE ROUTE SHOWING COMPLIANCE WITH SLOPE REQUIREMENTS OF ICC 117.1, SECTION 403.3. 3.WIDTH OF ACCESSIBLE ROUTES TO BE 4' MIN AS PER DEVELOPMENT STANDARDS. II. SITE PLAN SHEET, 2 OF 3: A.PROVIDE ONE ACCESSIBLE PARKING SPACES AS PER 2006 IBC, SECTION 1106; ICC 117.1, SECTION 503. PROVIDE LARGE SCALE DETAILS SHOWING SIZE OF SPACE AND ISLE, SIGNAGE, ACCESSIBLE ROUTE AND GRADE SLOPES. B.SURFACE SLOPES FOR ALL ACCESSIBLE PARKING AREAS TO BE NO GREATER THAN 1:48, ICC 117.1, SECTION 502.5. PROVIDE SPOT GRADES REFLECTING COMPLIANCE C.ALL RIGHT OF WAY CURB RAMPS TO MEET COT, DOT STANDARDS 207 D.ALL PRIVATE PROPERTY CURB RAMPS TO MEET 2006 IBC/ICC 117.1 ACCESSIBLE STANDARDS, SECTION 406. III. SHEET A.100: A. PROVIDE ARCHITECTS SEAL, SIGNATURE AND REQUIRED DATES. B.FINISH FLOOR PLAN DETAILING AND DIMENSIONING C.NEITHER TOILET ROOM IS ACCESSIBLE. REDESIGN AS PER IBC 1109, 1109.3, 1109.5, 1110 AND ICC 117.1 301, 401 AND 601. 1.PROVIDE LARGE SCALE FLOOR PLANS SHOWING ALL REQUIRED CLEARANCES AND ALL ROOM ELEVATIONS SHOWING ALL REQUIRED ACCESSORIES AND MOUNTING. D. PROVIDE ACCESSIBLE WATER COOLERS AND A SERVICE SINK, IBC 2006, SECTION 2902 IV. SHEET A.200: A. PROVIDE ARCHITECTS SEAL, SIGNATURE AND REQUIRED DATES. B. FINISH ELEVATION DETAILING AND DIMENSIONING C.PROVIDE THE FOLLOWING ARCHITECTURAL DETAILING NOT SHOWN: 1. ROOF PLAN AND DETAILS 2. ROOM, DOOR AND HARDWARE SCHEDULES 3. BUILDING SECTIONS 4. WALL SECTIONS 5. AND ETC V. SHEET A2: A. SHOULD THIS SHEET BE D-2? B. PROVIDE STRUCTURAL ENGINEER'S SEAL C. PROVIDE STRUCTURAL ENGINEER'S CALCULATIONS D. SHOW SECOND TOILET ROOM AS PER ARCHITECTURAL FLOOR PLAN E. FOUNDATION DESIGN DOES NOT WORK, REDESIGN AND DETAILING TO BE BY A CERTIFIED STRUCTURAL ENGINEER REGISTERED IN THE STATE OF ARIZONA. F. PROVIDE STRUCTURAL CALCULATIONS FOR METAL BUILDING DESIGN. END OF REVIEW |
| 04/18/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 04/25/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. 3. Provide a complete plumbing plan. See the submittal requirements at: http://www.tucsonaz.gov/dsd/Permit_Review_/Commercial/Submittal_Requirements.pdf Reference: Section 103.2.3, UPC 2006. 4. Coordinate the floor plans, fixture schedule, fixture specifications, and the general notes so that they apply to the same project. Reference: Section 103.2.3, UPC 2006. 5. Provide a connection to the public sewer system for all of the plumbing fixtures. Reference: Section 305.0, UPC 2006 6. Provide fixture descriptions or material standards for all plumbing fixtures, including those being provided by others. Reference: Section 401.1, UPC 2006. 7. Show how the installation of the water heater (heaters ?) complies with the requirements of Section 508, UPC 2008. 8. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief, and valves. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006. 9. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
| 04/25/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide ventilation calculations and design of a mechanical ventilation system for the enclosed parking garages per Sections 403 and 404, IMC 2006. 3. Demonstrate energy code compliance. Reference: Section 101.4, International Energy Conservation Code 2006. |
| 04/25/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the site utility plan showing the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf 2. Provide site utility plan showing the size and route of the building water supply along with the location and size of the water meter. Reference: Section 103.2.3, UPC 2006 |
| 04/28/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical plans shall be prepared, sealed, signed, and dated by a Registrant in the State of Arizona. No electrical review performed. |
| 05/12/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | 1:GARAGE BLDG #1 & STORAGE BLDG #2 2:CONNECTING TO EXSISTING ON SITE 4" HCS PER DRAWINGS ( NEED TO VERIFY PRIOR PERMITTING-FRONTS 27" PUBLIC SEWER G-91-020 & FRONTS 66" PUBLIC SEWER G-89-012) 3:NEED TO REVIEW FLOOR PLAN & PLUMBING PLAN(DO NOT MATCH) 4:NEED WASTEWATER CREDIT EVALUATION FOR ANY BUILDINGS DEMOLISHED. |
| 05/14/2008 | HEATHER THRALL | ZONING | REVIEW | Denied | Once building/structural division reviews and approves the building plans, zoning can continue the review of the building plans for compliance with the approved site plan. Please resubmit the building plans with a copy of the last approved site plan. Ensure all building heights on the building plans have notations from grade to top of walls, and grade to roof for heights. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/20/2008 | SUE REEVES | REJECT SHELF | Completed |
| 05/20/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 05/20/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |