Permit Number: T08CM01206
Parcel: 11612118D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01206
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/29/2008 ROBERT SHERRY WATER REVIEW Approved
04/29/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show that the hub drain complies with Sections 411.1 and 804.1, UPC 2006.
2. The temperature of the hot water supply to the public lavatories shall be controlled to a maximum temperature of 110 degrees Fahrenheit. Reference: Section 504.3, IECC 2006.
3. Provide a pressure-absorbing device for the water connections to the urinal. Reference:: Section 609.10, UPC 2006
4. Provide calculations showing how the water distribution piping has been sized. Reference: Sections 610.4 and 610.5, UPC 2006.
5. Provide indirect waste piping for the prep sink. Reference: Section 801.2, UPC 2006.
6. Note that while the specified size of the gravity grease interceptor is correct, the sizing calculation shown on sheet P1.0 is incorrect. The 2006 UPC does not have an Appendix H and the sizing methods for both the gravity and hydromechanical grease interceptors have changed completely.
04/29/2008 ROBERT SHERRY WATER REVIEW Approved
04/30/2008 CAGUILA1 WWM REVIEW Needs Review