Permit Number: T08CM01180
Parcel: 12501026D

Address:
2323 E 10TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01180
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Detail 4/M2 does not show any structure and the structural calculations do not relate to the installation. Show how the fan coil unit is attached to the structure and show that the structure is capable of supporting the unit.
05/13/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Please see previous review comment. Mechanical and Electrical still do not coordinate.
05/28/2008 CPIERCE1 WWM REVIEW Needs Review
05/28/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/28/2008 CPIERCE1 FIRE REVIEW Needs Review