Permit Number: T08CM01180
Parcel: 12501026D

Address:
2323 E 10TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01180
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2008 HEATHER THRALL ZONING REVIEW Approved
04/15/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the fan coil unit is attached to the structure and show that the structure is capable of supporting the unit.
04/15/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01180 4/15/08

1. Fan Coil Unit Schedule on Sheet M1 specifies a unit which draws 5.2A. Electrical powers a 7.5 HP unit, which draws 24.2A. Please coordinate with Mechanical and clarify.
2. Condensing Unit Schedule specifies a unit with 38.1 MCA. Electrical provides for a 58.8 MCA unit. Please clarify.
04/15/2008 ROBERT SHERRY WATER REVIEW Approved
04/15/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/15/2008 JASON GREEN ENGINEERING REVIEW Approved
04/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide sizing calculations (i.e. what is the roof area served) for the scupper noted in detail 2/ A5.1. How is the overflow provided for the roof?
05/07/2008 DROBEY1 WWM REVIEW Needs Review
05/07/2008 DROBEY1 FIRE REVIEW Needs Review
05/07/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2008 DELMA ROBEY OUT TO CUSTOMER Completed