Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01180
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
04/15/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the fan coil unit is attached to the structure and show that the structure is capable of supporting the unit. |
04/15/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01180 4/15/08 1. Fan Coil Unit Schedule on Sheet M1 specifies a unit which draws 5.2A. Electrical powers a 7.5 HP unit, which draws 24.2A. Please coordinate with Mechanical and clarify. 2. Condensing Unit Schedule specifies a unit with 38.1 MCA. Electrical provides for a 58.8 MCA unit. Please clarify. |
04/15/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/15/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/15/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
04/15/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide sizing calculations (i.e. what is the roof area served) for the scupper noted in detail 2/ A5.1. How is the overflow provided for the roof? |
05/07/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
05/07/2008 | DROBEY1 | FIRE | REVIEW | Needs Review | |
05/07/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/07/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |