Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01176
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/14/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/14/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM01176 4/14/08 1. Ampacity of #8 conductor, 50A, is not sufficient for the load on panel P1FC. 2. Size of secondary conductor on XFMR TFC is too small per NEC 240.21 (c) (2) (a) and (b). |
| 04/14/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/14/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/14/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 04/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/14/2008 | DAVE MANN | FIRE | REVIEW | Denied | Plan states building is not sprinklered. Consequently, corridor needs a 1 hour fire rating, per 2006 IFC, Section 1017.1. |
| 04/18/2008 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 04/18/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |