Permit Number: T08CM01176
Parcel: 13316030E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01176
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2008 STEVE SHIELDS ZONING REVIEW Approved
04/14/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM01176 4/14/08

1. Ampacity of #8 conductor, 50A, is not sufficient for the load on panel P1FC.
2. Size of secondary conductor on XFMR TFC is too small per NEC 240.21 (c) (2) (a) and (b).
04/14/2008 ROBERT SHERRY WATER REVIEW Approved
04/14/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/14/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/14/2008 DAVE MANN FIRE REVIEW Denied Plan states building is not sprinklered. Consequently, corridor needs a 1 hour fire rating, per 2006 IFC, Section 1017.1.
04/18/2008 CAGUILA1 WWM REVIEW Needs Review
04/18/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review