Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T08CM01171
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 14. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole or cleanout in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Section 710.1, UPC 2006, as amended by the City of Tucson. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/17/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |