Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Approved PLAN CHECK COMMENTS - PROJECT #T08CM01166

8/02/08 1418 N. LOUIS AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



SECTIONS - DETAILS - MISC. NOTES:

1. Outdoor Lighting Code :
1. The security lights are listed at 150 watts for each bulb per fixture, not 11 watts. Section 4.16.2
Requires the brightest bulb listed for the fixture to be used for lumen calculation. Call me ! there is a
way to shield the fixture which would remove the lumens from the count.

2. Provide cut sheets for the 150 watt bulbs.

3. Include the fluorescents in the carport in the calculations.

4. Section 5.1.2 negates the lumen emitted from "Full Cut Off" fixtures, as defined by section 5.1.2,
If they are under canopies, overhangs, or eaves. Not all fixture types qualify for this negation. See
section 4.7 for the definition of full cut off fixtures.

5. All exterior lights are to be included in the lumen count according to section 3.1.2. i.e. the
Existing fixture on porch#1. Are there other lights; light kit on the fan shown on porch #2?







IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2008 GERARDO BONILLA APPROVAL SHELF Completed
08/21/2008 DELMA ROBEY OUT TO CUSTOMER Completed
08/21/2008 DELMA ROBEY REJECT SHELF Completed