05/14/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T08CM01155

5/16/08 1418 N. LOUIS AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

FOUNDATION PLANS:

1. PLEASE PROVIDE A LANDING FOR THE EXTERIOR SIDE OF THE 3068 IN THE NORTH WALL OF THE SHOP. SEE R311.4.3 .

STRUCTURAL PLANS:

1. PLEASE DOUBLE THE TWO TRIMMER JOISTS, OR EQUAL, AT EACH SIDE OF THE FIREPLACE. SEE R802.9 .

2. FRAMING PLANS / A1.1 ; PROVIDE THE DOOR AND WINDOW OPENINGS, WIDTHS, IN THE EXISTING WALLS AT THE ADDED PORCHES. IS THE 4X6 IN 1 / A1.1 THE ONLY HEADER FOR THE EXISTING OPENINGS?

3. FRAMING PLAN-WORKSHOP / A1.1 ; SINGLE SPAN OUTRIGGERS WON'T SUPPORT THE FLYRAFTER. PLEASE ILLUSTRATE THEM SPANNING TO THE SECOND TRUSS AND MAKE SURE THE TRUSS COMPANY KNOWS THE TOP CHORD OF THE GABLE TRUSS WILL BE NOTCHED. OR JUSTIFY THE SINGLE SPAN.

4. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS DATA MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

5. DETAIL GABLE END BRACING CONNECTIONS.

SECTIONS - DETAILS - MISC. NOTES:

1. 2 / A1.0 ; PROVIDE THE SIZE OF THE FIREBOX. R1001.6 .

2. 2 / A1.0 ; ILLUSTRATETHE SMOKE SHELF (CHAMBER), DAMPER, AND FLUE SIZE. R1001.6, TABLE 1001.1

3. 2 / A1.0 ; PROVIDE THE VERTICAL REINFORCEMENT AND BOND BEAM AT THE CHIMEY'S TOP. TABLE R1001.1

4. 2 / A1.1 ; SIZE THE LINTEL OVER THE FIREBOX OPENING.

5. 2 / A1.0 ; DIMENSION THE FOOTING FOR THE FIRE PLACE. TABLE R1001.1

6. 1 / A1.3 ; PROVIDE REINFORCEMENT FOR THE FOOTING.

7. 1 / A3.0 ; CC68 ISN'T APPROVED FOR MASONRY CONNECTIONS. DID YOU MEAN CCO 6 1/8 W / 2-#5 X 24" OR SOMETHING LIKE THAT? CHECK THE SPEC'D GLUE-LAM SIZE. IT'S OKAY, BUT IT'S NOT A STOCK SIZE.

8. 1, 2 /A3.0 ; MTS IS A CONNECTION BETWEEN TWO WOOD MEMBERS. SIMPSON'S CATALOG SHOWS IT NAILED TO THE BOTTOM OF THE PLATE TO USE ALL THE NAIL HOLES. IF YOU WANT TO DO THIS ON A MASONRY WALL, IT'S OKAY.

9. 5 / A3.0 ; PLEASE CHANGE "FIN. GRADE" TO UNDISTURBED GRADE OR NATURAL GRADE. R403.1.4

10. 6 / A3.0 ; PLEASE CHANGE THE EDGE NAILING TO 6"OC AND SPECIFY THE NAILS.

ELECTRICAL PLANS:

1. PROVIDE A WALL SWITCHED LIGHT OUTSIDE THE 3068 IN THE NORTH WALL OF THE SHOP. E3803.3

2. PLEASE SHOW THE LOCATION OF THE ELECTRICAL SUB-PANEL.

3. OUTDOOR LIGHTING CODE / E1.0 ; INCLUDE THE LIGHT AT THE SHOP AND THE EXISTING LIGHTS IN THE CALCULATIONS.

4. OUTDOOR LIGHTING CODE / E1.0 ; THE 8400 LUMENS EXCEED THE LUMENS ALLOWED FOR A .17 ACRE LOT. THE LUMEN COUNT USED IS PER ACRE, 43560 SQUARE FEET. ARE ANY OF THESE FIXTURES "FULL CUTOFF" FIXTURES AS DEFINED IN4.7 OF THIS CODE WHICH WOULD POSSIBLY ALLOW YOU TO TAKE ADVANTAGE OF THE EXCEPTION MENTIONED IN 5.1.2 OF THIS CODE?

5. PROVIDE CUT SHEETS FOR THE NEW FIXTURES.

6. JUSTIFY 700 LUMENS FOR A 75 WATT BULB.

7. ELECTRIC GENERAL NOTE 4 / E1.1 ; WHAT DOES "OTHOGONAL" MEAN?

8. ELECTRIC PANEL SCHEDULE / E1.1 ; DO YOU WANT THE PANEL FED FROM THE TOP OR BOTTOM?



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: