Review Details: REVISION - - 2ND
Permit Number - T08CM01163
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/31/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 09/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the discharge point of the elevator sump pump; it is not permissible to discharge to the storm water system. Reference: Section 1104.0, UPC 2006. 2. Revise the condensate waste detail on sheet M701 to comply with the requirements of Section 1001.4 (maximum tailpiece length 24") and Section 1007.0 (trap seal protection), UPC 2006. |
| 09/14/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 09/15/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 09/17/2009 | SUE REEVES | REJECT SHELF | Completed |