Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T08CM01163
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: REI at Tucson Mall T08CM01163 Building Plan (2nd Review) TRANSMITTAL DATE: July 2, 2008 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Provide a copy of the approved and stamped CDRC Development Plan with the next submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t08cm01163.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved development plan and additional requested documents |
| 07/02/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not addressed. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 07/03/2008 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/15/2008 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 07/15/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |