Permit Number: T08CM01163
Parcel: 10511061E

Address:
160 W WETMORE RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM01163
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
06/09/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/10/2008 DAVE MANN FIRE REVIEW Denied Design criteria for Mercantile occupancies is Ordinary Group 2, which has a design density of .2 over 2000 sq. ft. Information on page F001 is incorrect. Also, please reference 2006 NFPA 13 and explain in detail how the density for the storage areas was determined (code section, curve used, etc.).
06/10/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: REI at Tucson Mall
T08CM01163
Building Plan (1st Review)

TRANSMITTAL DATE: June 10, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Provide a copy of the approved and stamped CDRC Development Plan with the next submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm01163.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved development plan and additional requested documents
06/19/2008 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
06/26/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/01/2008 GERARDO BONILLA REJECT SHELF Completed