| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/09/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 06/10/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: REI at Tucson Mall T08CM01163 Building Plan (1st Review) TRANSMITTAL DATE: June 10, 2008 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Provide a copy of the approved and stamped CDRC Development Plan with the next submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t08cm01163.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved development plan and additional requested documents |
| 06/10/2008 | DAVE MANN | FIRE | REVIEW | Denied | Design criteria for Mercantile occupancies is Ordinary Group 2, which has a design density of .2 over 2000 sq. ft. Information on page F001 is incorrect. Also, please reference 2006 NFPA 13 and explain in detail how the density for the storage areas was determined (code section, curve used, etc.). |
| 06/19/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 06/26/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/01/2008 | GERARDO BONILLA | REJECT SHELF | Completed |