| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/13/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/14/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. The water calculations indicate a demand of only 7 GPM but the connected load shows a demand of 18 GPM. A 1" water meter will be required by Tucson Water. |
| 05/20/2008 | CAGUILA1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/20/2008 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 05/20/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |