Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01129
Parcel: 13355231A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01129
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/30/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/30/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the condensate drain pipes per Section 307.2.2, IMC 2006, as amended by the City of Tucson.
2. The relative locations of the restroom exhaust fans are not an issue. Turning off the fans while the building is occupied will result in the air supplied to the restrooms being recirculated to the rest of the building. Revise the sequence of operation for the restroom exhaust fans to ensure that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006.
06/10/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Distance from Panel L2 to Panel X appears to be aprox. 33', not 45'. Available fault current at Panel X appears to be greater than 13KA, not less than 10KA.