Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM01129
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/30/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/30/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the condensate drain pipes per Section 307.2.2, IMC 2006, as amended by the City of Tucson. 2. The relative locations of the restroom exhaust fans are not an issue. Turning off the fans while the building is occupied will result in the air supplied to the restrooms being recirculated to the rest of the building. Revise the sequence of operation for the restroom exhaust fans to ensure that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006. |
| 06/10/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Distance from Panel L2 to Panel X appears to be aprox. 33', not 45'. Available fault current at Panel X appears to be greater than 13KA, not less than 10KA. |