Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01129
Parcel: 13355231A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01129
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/11/2008 MARTIN BROWN FIRE REVIEW Approved
04/14/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; CODE INFORMATION: REPLACE 1992 ADAAG REFERENCE WITH ICC/ANSI A117.1-2003. VERIFY COMPLIANCE FOR ALL ACCESSIBILITY ISSUES.
2. SHEET A5.2; DETAIL 8: RELOCATE TOILET PAPER DISPENSER PER ANSI FIGURE 604.7.
3. SHEET A5.2; DETAIL 8: LENGTH OF VERTICAL GRAB BAR MAY BE REDUCED PER ANSI FIGURE 604.5.1.
4. SHEET A4.1; DETAILS 1/2/3/6: SINKS INDICATED IN THESE DETAILS MUST MEET ANSI SECTION 606.3 FOR HEIGHT ACCESSIBILITY.
5. SHEET A2.1; DETAIL 2: VERIFY TOILET 2 MEETS ANSI SECTION 304.3.1 AND SECTION 306 FOR ACCESSIBILITY.
04/21/2008 ROBERT SHERRY WATER REVIEW Approved
04/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide water supply isometrics. Reference: Section 103.2.3, UPC 2006.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. The use of a water heater thermostat for this purpose is not allowed. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
04/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. All possible locations for the termination of the existing condensate drains appear to have been removed during the demolition of the shell interior. Show how the condensate is to be piped and terminated. Reference: Sections 106.3.1 and 307.2.1, IMC 2006, as amended by the City of Tucson.
3. Revise the sequence of operation for the restroom exhaust fans to ensure that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006.
4. Revise the note on detail 1/M3.1 to comply with the requirements of Section 501.2.1 (4): environmental air exhaust ducts shall terminate at least 10 feet from mechanical air intakes.
04/24/2008 GERRY KOZIOL WWM REVIEW Approved
04/30/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
2. Provide for grounding of the telephone system. Reference NEC 800.100.
3. Please add that all work in patient care areas shall comply with NEC 517.13.
4. It does not seem likely that the utility, TEP, would give the customer the available fault current at the service entrance. For a 208/120V, 3000A service the utility publishes 75,100A at the secondary of the utility transformer, with the guidance that the utility should be consulted as to whether the transformer will be sized to serve more than one customer.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2008 CPIERCE1 OUT TO CUSTOMER Completed
05/15/2008 SHANAE POWELL REJECT SHELF Completed