Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01129
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/09/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/11/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/14/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; CODE INFORMATION: REPLACE 1992 ADAAG REFERENCE WITH ICC/ANSI A117.1-2003. VERIFY COMPLIANCE FOR ALL ACCESSIBILITY ISSUES. 2. SHEET A5.2; DETAIL 8: RELOCATE TOILET PAPER DISPENSER PER ANSI FIGURE 604.7. 3. SHEET A5.2; DETAIL 8: LENGTH OF VERTICAL GRAB BAR MAY BE REDUCED PER ANSI FIGURE 604.5.1. 4. SHEET A4.1; DETAILS 1/2/3/6: SINKS INDICATED IN THESE DETAILS MUST MEET ANSI SECTION 606.3 FOR HEIGHT ACCESSIBILITY. 5. SHEET A2.1; DETAIL 2: VERIFY TOILET 2 MEETS ANSI SECTION 304.3.1 AND SECTION 306 FOR ACCESSIBILITY. |
04/21/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/21/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. Provide water supply isometrics. Reference: Section 103.2.3, UPC 2006. 3. Show how the temperature of the hot water supply to the public lavatories is controlled. The use of a water heater thermostat for this purpose is not allowed. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
04/21/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. All possible locations for the termination of the existing condensate drains appear to have been removed during the demolition of the shell interior. Show how the condensate is to be piped and terminated. Reference: Sections 106.3.1 and 307.2.1, IMC 2006, as amended by the City of Tucson. 3. Revise the sequence of operation for the restroom exhaust fans to ensure that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006. 4. Revise the note on detail 1/M3.1 to comply with the requirements of Section 501.2.1 (4): environmental air exhaust ducts shall terminate at least 10 feet from mechanical air intakes. |
04/24/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
04/30/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Provide for grounding of the telephone system. Reference NEC 800.100. 3. Please add that all work in patient care areas shall comply with NEC 517.13. 4. It does not seem likely that the utility, TEP, would give the customer the available fault current at the service entrance. For a 208/120V, 3000A service the utility publishes 75,100A at the secondary of the utility transformer, with the guidance that the utility should be consulted as to whether the transformer will be sized to serve more than one customer. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/15/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
05/15/2008 | SHANAE POWELL | REJECT SHELF | Completed |