Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM01103
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2008 GERRY KOZIOL WWM REVIEW Approved
05/07/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-08-08
Activity: T08CM01103
Address: 3702 S. Lundy Ave
Applicant: Babriel Manriquez

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

ELEVATIONS:
3. Specify metal roofing type, grade of materials, and method of installation, R905.

SECTIONS - DETAILS:
4. Specify ceiling covering. Note: Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.

PLUMBING PLAN:
5. Provide an accurate fixture unit schedule required for the entire property (including existing) UPC Tables 6-5 and 7-3.

MECHANICAL PLAN:
6. Provide return air duct and register size sized according to M1403.1. Minimum duct/register size: heat pump or air conditioner - 6 sq. in. / 1000 BTU with louver reduction factor (75% for metal grills) G2407.10.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review